Version: blank
Install
hydrapwk@hydrapwk:~$ sudo apt install modpoll
Updated on: 30 September 2025
By: Joe
Edit this pages
Tool Documentation:
$ modpoll --helpModpoll v1.5.0 - A New Command-line Tool for Modbus and MQTT
usage: modpoll [-h] [-v] -f CONFIG [CONFIG ...] [-d] [-r RATE] [-1]
[--interval INTERVAL] [--tcp TCP] [--tcp-port TCP_PORT]
[--udp UDP] [--udp-port UDP_PORT] [--rtu RTU]
[--rtu-baud RTU_BAUD] [--rtu-parity {none,odd,even}]
[--timeout TIMEOUT] [-o EXPORT] [--mqtt-version {3.1.1,5.0}]
[--mqtt-host MQTT_HOST] [--mqtt-port MQTT_PORT]
[--mqtt-clientid MQTT_CLIENTID]
[--mqtt-topic-prefix MQTT_TOPIC_PREFIX]
[--mqtt-publish-topic-pattern MQTT_PUBLISH_TOPIC_PATTERN]
[--mqtt-subscribe-topic-pattern MQTT_SUBSCRIBE_TOPIC_PATTERN]
[--mqtt-diagnostics-topic-pattern MQTT_DIAGNOSTICS_TOPIC_PATTERN]
[--mqtt-qos {0,1,2}] [--mqtt-user MQTT_USER]
[--mqtt-pass MQTT_PASS] [--mqtt-use-tls] [--mqtt-insecure]
[--mqtt-cacerts MQTT_CACERTS]
[--mqtt-tls-version {tlsv1.2,tlsv1.1,tlsv1}] [--mqtt-single]
[--diagnostics-rate DIAGNOSTICS_RATE] [--autoremove]
[--loglevel {DEBUG,INFO,WARNING,ERROR,CRITICAL}] [--timestamp]
[--delay DELAY] [--framer {default,ascii,binary,rtu,socket}]
Modpoll v1.5.0 - A New Command-line Tool for Modbus and MQTT
options:
-h, --help show this help message and exit
-v, --version show program's version number and exit
-f, --config CONFIG [CONFIG ...]
A local path or URL of Modbus configuration file.
Required!
-d, --daemon Run in daemon mode without printing result.
Recommended to use with docker
-r, --rate RATE The sampling rate (s) to poll modbus device, Defaults
to 10.0
-1, --once Only run polling at one time
--interval INTERVAL The time interval in seconds between two polling,
Defaults to 0.5
--tcp TCP Act as a Modbus TCP master, connecting to host TCP
--tcp-port TCP_PORT Port for MODBUS TCP. Defaults to 502
--udp UDP Act as a Modbus UDP master, connecting to host UDP
--udp-port UDP_PORT Port for MODBUS UDP. Defaults to 502
--rtu RTU pyserial URL (or port name) for RTU serial port
--rtu-baud RTU_BAUD Baud rate for serial port. Defaults to 9600
--rtu-parity {none,odd,even}
Parity for serial port. Defaults to none
--timeout TIMEOUT Response time-out seconds for MODBUS devices, Defaults
to 3.0
-o, --export EXPORT The file name to export references/registers
--mqtt-version {3.1.1,5.0}
MQTT version. Defaults to MQTT v3.1.1
--mqtt-host MQTT_HOST
MQTT server address. Skip MQTT setup if not specified
--mqtt-port MQTT_PORT
1883 for non-TLS or 8883 for TLS, Defaults to 1883
--mqtt-clientid MQTT_CLIENTID
MQTT client name, If qos > 0, set unique name for
multiple clients
--mqtt-topic-prefix MQTT_TOPIC_PREFIX
(DEPRECATED) Topic prefix for MQTT
subscribing/publishing. Defaults to None
--mqtt-publish-topic-pattern MQTT_PUBLISH_TOPIC_PATTERN
Topic pattern for MQTT publish. Use as
placeholder for the device names in Modbus config.
Defaults to "modpoll//data"
--mqtt-subscribe-topic-pattern MQTT_SUBSCRIBE_TOPIC_PATTERN
Topic pattern for MQTT subscribe. Defaults to
"modpoll/+/set"
--mqtt-diagnostics-topic-pattern MQTT_DIAGNOSTICS_TOPIC_PATTERN
Topic pattern for MQTT diagnostics. Use
as placeholder for the device names in
Modbus config. Defaults to
modpoll//diagnostics
--mqtt-qos {0,1,2} MQTT QoS value. Defaults to 0
--mqtt-user MQTT_USER
Username for authentication (optional)
--mqtt-pass MQTT_PASS
Password for authentication (optional)
--mqtt-use-tls Use TLS
--mqtt-insecure Use TLS without providing certificates
--mqtt-cacerts MQTT_CACERTS
Path to ca keychain
--mqtt-tls-version {tlsv1.2,tlsv1.1,tlsv1}
TLS protocol version, can be one of tlsv1.2 tlsv1.1 or
tlsv1
--mqtt-single Publish each value in a single topic. If not
specified, groups all values in one topic.
--diagnostics-rate DIAGNOSTICS_RATE
Time in seconds as publishing period for each device
diagnostics
--autoremove Automatically remove poller if modbus communication
has failed 3 times.
--loglevel {DEBUG,INFO,WARNING,ERROR,CRITICAL}
Set log level, Defaults to INFO
--timestamp Add timestamp to the result
--delay DELAY Time to delay sending first request in seconds after
connecting. Default to 0
--framer {default,ascii,binary,rtu,socket}
The type of framer for modbus message. Use default